Get Latest Final Year ECE/EEE Projects in your Email

Your Email ID:
FYP.in Subs

Earth Fault Location Based on Evaluation of Voltage Sag at Secondary Side of Medium Voltage/low Voltage Transformers

Download Project:

Fields with * are mandatory

Abstract

The main reasons for installation of power quality meters in distribution transformer substations are power quality monitoring and global evolution of electrical network towards the `smart grid’. In case that all measurements from the meters are properly synchronised and centralised, new possibilities of control or evaluation of the network are enabled.

This contribution proposes the possibility for an earth fault localisation with the aid of synchronised data recorded on the low-voltage side of the medium voltage/low voltage transformers in compensated neutral distribution networks which are equipped with auxiliary resistor for short-time increasing of the active part of the fault current.

The described method uses voltage sags evoked by connecting of the auxiliary resistor for locating the faulty section. The proposed method is tested with the help of numerical model which presents a part of the distribution network. Based on the simulation results, it is confirmed that the principle ofthe described method is useful for delimiting of faulty section incompensated networks during solid and low-impedance EFs. Sincethe sensitivity of the method strongly depends on the fault currentlevel and thus on a fault resistance, the sensitivity of faulty sectiondefinition during high-impedance EF is very low.

Source: IEEE
Authors: David Topolanek | Matti Lehtonen | Mohd Rafi Adzman | Petr Toman

Download Project

Download Project:

Fields with * are mandatory